Fault Clearing Overvoltages on Long Transformer Terminated Lines
Document Type
Periodical
Source
IEEE Transactions on Power Apparatus and Systems IEEE Trans. Power Appar. Syst. Power Apparatus and Systems, IEEE Transactions on. PAS-98(2):667-678 Mar, 1979
Subject
Power, Energy and Industry Applications
Components, Circuits, Devices and Systems
Surges
Circuit breakers
Circuit faults
Arresters
Distributed parameter circuits
Power system transients
Switching circuits
Resistors
Transient analysis
Stress
Language
ISSN
0018-9510
Abstract
The results of Transient Network Analyzer (TNA) studies evaluating the feasibility of low-side switching long transformer terminated lines is reported. It is shown that overvoltages following line dropping and fault clearing can severely stress surge arresters and circuit brtakers exceeding capabilities specified in ANSI standards. These overvoltages are often not carefully considered in design studies, since the available literature on low-side switching of EHV transmission lines primarily deals with energizing the line and transformer.1,2,3,4