Calibration System for High-Voltage Transformers With Multiharmonic Distorted Waveforms
Document Type
Periodical
Source
IEEE Transactions on Instrumentation and Measurement IEEE Trans. Instrum. Meas. Instrumentation and Measurement, IEEE Transactions on. 73:1-13 2024
Subject
Power, Energy and Industry Applications
Components, Circuits, Devices and Systems
Harmonic analysis
Voltage measurement
High-voltage techniques
Frequency measurement
Power system harmonics
Transducers
Frequency response
Discrete Fourier transform
frequency response (FR) measurement
harmonic analysis
instrument voltage transformers
measurement uncertainty
power quality
Language
ISSN
0018-9456
1557-9662
Abstract
Non-ideal frequency response (FR) and voltage non-linearity of high-voltage (HV) instrument transformers directly impact the accuracy of HV measurements in the presence of harmonics. Characterization of voltage instrument transformer FR is generally performed at low voltage (LV) with sinusoidal test signals. Those results may not accurately represent the response of the instrument transformer when subjected to distorted waveforms in modern power systems. This article presents a calibration system for the evaluation of harmonic measurement accuracy of single-phase instrument transformers with rated voltages up to 132/ $\surd 3$ kV using multitone test signals containing a HV fundamental component and superimposed harmonics up to 10 kHz. Such signals would represent the realistic operating conditions of HV instrument transformers. The performance of the developed system was analyzed by obtaining the voltage ratio and phase displacement of the reference capacitive voltage divider (CVD) from 50 Hz to 10 kHz at 1 kV with an expanded uncertainty of 0.07% for the voltage ratio error and 0.09 crad for the phase error. The effect of voltage linearity at harmonic frequencies and the effect of the fundamental voltage on the errors of the measurements of harmonics were also evaluated. The results prove that the system is capable of calibrating HV instrument transformers under distorted waveform conditions with an uncertainty of 0.13% for ratio and 0.15 crad for phase error at harmonic frequencies from 100 Hz to 10 kHz, and 0.02% and 0.04 crad at the fundamental power frequency of 50 Hz.