학술논문

On the Assessment of Sampling Rate Impacts on Responses of Digital Protective Relays
Document Type
Periodical
Source
IEEE Transactions on Industry Applications IEEE Trans. on Ind. Applicat. Industry Applications, IEEE Transactions on. 59(5):5420-5431 Jan, 2023
Subject
Power, Energy and Industry Applications
Signal Processing and Analysis
Fields, Waves and Electromagnetics
Components, Circuits, Devices and Systems
Protective relaying
Protocols
Time-frequency analysis
Current measurement
Synchronization
Relays
Power systems
IEC 61850 Sampled Values
digital protective relays
87 T transformer digital differential protection
process bus
data sampling
sampling rates
and real-time implementation
Language
ISSN
0093-9994
1939-9367
Abstract
Power systems (including industrial and commercial power systems) widely utilize digital protective relays for component and system protection. These protective devices have shown numerous operational advantages over conventional electromagnetic protective devices. Such operational advantages include the accuracy, reliability, response speed, interoperability, weight, and size. Performance and operational advantages of digital protective relays are typically dependent on the resolution of their input data, as well as their algorithms for fault detection and identification. This article assesses the performance of time-based, frequency-based, and time-frequency-based digital protective relays, when operated at different sampling rates. Tested sampling rates include low, medium, and high sampling rates that range from 16 to 288 samples per cycle. In this article, the three digital protective relays are tested when deployed as the digital 87 T transformer digital protection. Performance of the time-based, frequency-based, and time-frequency-based digital protective relays is assessed in terms of their accuracy and response speed. Test results show that low sampling rates can deteriorate the accuracy and response speed of the three tested digital protective relays. Obtained performance results also reveal that medium and high sampling rates can effectively improve the accuracy and response speed of the time-based, frequency-based, and time-frequency-based digital protective relays.