학술논문

이중 퀜치를 이용한 변압기형 초전도 한류기의 권선전류와 초전도소자 저항에 따른 전력소모 및 누적에너지 분석
Analysis on Power Consumption and Accumulated Energy According to Resistance of Superconducting Element and Winding Current of Transformer Type SFCL Using Double Quench
Document Type
Article
Source
전기전자재료학회논문지(J. Korean Inst. Electr. Electron. Mater. Eng.) / Journal of the Korean Institute of Electrical and Electronic Material Engineers. Oct 01, 2016 29(10):630
Subject
Power consumption
Accumulated energy
Transformer type SFCL (superconducting fault current limiter)
Double quench
Language
Korean
ISSN
1226-7945
Abstract
In this paper, we analyzed the power consumption and the accumulated energy in HTSC (high-TC superconducting elements) according to the resistance of HTSC element and the winding current of transformer type SFCL (superconducting fault current limiter) using double quench. For the analysis, two different inductances of the one secondary winding among two secondary windings comprising the transformer type SFCL were selected and the short-circuit tests were carried out. The consumed power and the accumulated energy in HTSC element connected into the secondary winding with larger inductance were analyzed to be larger compared to the one connected into the secondary winding with lower inductance.

Online Access