식품공장 건축물 바깥쪽으로의 출구 설치기준에 따른 RSET 분석
Analysis of RSET According to Exit Installation Standards for the Exterior of a Food Manufacturing Plant Building
Document Type
Article
Text
Source
The Journal of the Convergence on Culture Technology (JCCT), 03/31/2024, Vol. 10, Issue 2, p. 201-208
Subject
식품공장
건축법
건축물 바깥쪽으로의 출구 설치 기준
성능위주설계
ASET
RSET
피난안전성 평가
Food factory
Exit installation standards towards the outside of the building
ASET (Available Safe Egress Time)
RSET (Required Safe Egress Time)
Evacuation safety evaluation
Language
Korean
ISSN
2384-0358
Abstract
In this study, we investigated whether the evacuation time according to the exit installation standards specified in the building code during a food factory fire is compatible with the evacuation time based on the performance-based design specified by the fire department, in order to determine if evacuation safety is ensured. We used the Pathfinder program to confirm the evacuation time, and experimented with three scenarios for exit installation standards towards the outside of the building: 60m, 80m, and 100m. The target building in the experiment corresponded to the building code`s exit installation standard of 100m from each dwelling. The experimental results showed tt in the cases of 80m and 100m, ASET exceeded RSET, indicating tt evacuation safety was not ensured, while in the case of 60m, evacuation safety was maintained. Through this study, it was confirmed tt even when the exit installation standards towards the outside of the building are met, evacuation safety may not be guaranteed.