Instability of DC arc in SF/sub 6/ circuit breaker
Document Type
Periodical
Source
IEEE Transactions on Power Delivery IEEE Trans. Power Delivery Power Delivery, IEEE Transactions on. 12(4):1508-1513 Oct, 1997
Subject
Power, Energy and Industry Applications
Circuit breakers
Frequency
Power system reliability
Circuit testing
Capacitors
HVDC transmission
Interrupters
Impedance
Equations
Circuit faults
Language
ISSN
0885-8977
1937-4208
Abstract
Instability of the arc in an HVDC circuit breaker was investigated both analytically and experimentally. The analytical work showed that the amplification coefficient and the frequency of the oscillation that leads to the current zero can be given as functions of parallel impedance and arc characteristics. The process to estimate the arc characteristics from the amplification coefficient and the frequency experimentally observed was proposed and the result was compared with the estimation of the same characteristics by the analysis of the current zero behavior. It was shown that a description of the DC arc by a simple Mayr type model could reproduce the initiation and the growth of the oscillation and the interruption of the current.