학술논문

Cryogenic System for 80-kV DC HTS Cable in the KEPCO Power Grid
Document Type
Periodical
Source
IEEE Transactions on Applied Superconductivity IEEE Trans. Appl. Supercond. Applied Superconductivity, IEEE Transactions on. 25(3):1-4 Jun, 2015
Subject
Fields, Waves and Electromagnetics
Engineered Materials, Dielectrics and Plasmas
Superconducting cables
Cooling
High-temperature superconductors
Power cables
Heating
Nitrogen
DC superconducting power cable
cryogenic system
KEPCO
Stirling cryocooler
Language
ISSN
1051-8223
1558-2515
2378-7074
Abstract
DC HTS cable has advantages in the absence of ac loss. Therefore, the Korea Electric Power Corporation (KEPCO) has started a project of operating and manufacturing technology for applying an 80-kV 500-MW 500-m-long dc HTS cable to the commercial power grid since 2011. LS Cable Ltd. has joined this project for designing and manufacturing an HTS power cable, and KEPCO has taken on cryogenic system and real power grid operation. The cryogenic system for an 80-kV dc HTS cable is composed mainly of Stirling-type cryocoolers. The Stirling cryocooler has been examined and verified by real grid operation in Icheon substation, and we therefore became assured of reliability for the cooling HTS cable system. We present the cryogenic system design, installation, and some results of preliminary tests in this paper.