Sub-Synchronous Ferroresonance Causes Catastrophic Failure of a Line Shunt Reactor – A Post Mortem Investigation
Document Type
Periodical
Source
IEEE Transactions on Power Delivery IEEE Trans. Power Delivery Power Delivery, IEEE Transactions on. 37(1):374-382 Feb, 2022
Subject
Power, Energy and Industry Applications
Shunts (electrical)
Control systems
Switches
Circuit breakers
Shafts
Inductors
Surges
Ferranti effect
series and shunt compensated lines
low-frequency resonance
Language
ISSN
0885-8977
1937-4208
Abstract
On March 31, 2019, a 500 kV air-core, shunt reactor at a large generating station in BC Hydro was damaged shortly after four unit transformers were simultaneously energized from a 500 kV series and shunt compensated line source. Forensic investigations revealed that the controlled switching system, controlling the instant at which each breaker phase closes during energization to minimize inrush current, had failed. Uncontrolled closing led to under-damped, high-magnitude and sub-synchronous currents. Protection tripped and isolated the four transformers, followed shortly by shunt reactor protection tripping. Before the reactor could be isolated by circuit breakers, a damaging internal fault developed. This paper presents forensic investigation describing sequence of events leading up to reactor damage and shares the lessons learned with the peer utilities having similar installations.