학술논문

Research on KRT Monitoring Instrument Alarm Threshold in Main Control Room of Nuclear Power Plant
Document Type
Conference
Source
2019 Chinese Automation Congress (CAC) Chinese Automation Congress (CAC), 2019. :4022-4025 Nov, 2019
Subject
Aerospace
Communication, Networking and Broadcast Technologies
Components, Circuits, Devices and Systems
Computing and Processing
Power, Energy and Industry Applications
Robotics and Control Systems
Signal Processing and Analysis
Transportation
Accidents
Monitoring
Photonics
Layout
Ventilation
Xenon
Main control room
³-ray dose rate
Alarm threshold
Language
ISSN
2688-0938
Abstract
In this paper, the intake air gamma radioactive monitoring alarm threshold of nuclear plant main control room was studied for both under normal operation condition and accident conditions. According to two different layout schemes, gamma radiation dose rate of measuring point was calculated by the MCNP code under three typical accidents (including S3, DBA-LOCA and LOCA conditions). The results show that it is proper that to keep original value of the detector alarm threshold of improved main control room, it could provide effective radiation protection for indoor staff.