학술논문

Impact of utility switched capacitors on customer systems-magnification at low voltage capacitors
Document Type
Conference
Source
Proceedings of the 1991 IEEE Power Engineering Society Transmission and Distribution Conference Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society. :908-914 1991
Subject
Power, Energy and Industry Applications
Communication, Networking and Broadcast Technologies
Low voltage
Power system transients
Power factor correction
Surges
Switched capacitor circuits
Transient analysis
Power capacitors
Circuit simulation
Switching circuits
Power quality
Language
Abstract
The potential for magnified transient voltages at customer buses during capacitor switching on the primary distribution system is analyzed. The various factors affecting this phenomenon are analyzed in detail through extensive sensitivity analysis simulations. These factors include the switched capacitor size, short circuit capacity at the switched capacitor, customer step down transformer size, low voltage power factor correction, and customer load characteristics. The effects of these transients on customer equipment are described and possible solutions to control the transients are presented.ETX