Frequency Characterization of Medium Voltage Cables for Fault Prevention Through Multi-Valued Neural Networks and Power Line Communication Technologies
Document Type
Periodical
Source
IEEE Transactions on Power Delivery IEEE Trans. Power Delivery Power Delivery, IEEE Transactions on. 38(5):3227-3237 Oct, 2023
Subject
Power, Energy and Industry Applications
Power cables
Monitoring
Optical fiber cables
Medium voltage
Mathematical models
Location awareness
Conductors
Cable characterization
failure prevention
line modelling
medium voltage cables
multi-valued neurons
neural networks
power line communications
vector network analyzer
Language
ISSN
0885-8977
1937-4208
Abstract
This paper proposes a new prognostic method capable of preventing catastrophic failures in Medium Voltage (MV) power cables. The main objective is the development of a monitoring system focused on the detection and localization of cable overtemperatures in underground distribution networks. The predictive analysis proposed here is based on a Multi-Layer neural network with Multi-Valued Neurons (MLMVN), which elaborates measurements of high frequency signals transmitted through Power Line Communication (PLC) devices. Therefore, the prognostic method does not require the introduction of additional components since the power line is already equipped with a communication system. This allows low intrusion and the possibility of monitoring power lines during their operation. Furthermore, the MLMVN-based classifier processes magnitude and phase of the received signals without preliminary coding steps and ensures a low computational cost. The main theoretical concept on which the predictive analysis is based is the detection of malfunctions starting from their effects on the cable parameters. For this reason, an RG7H1M1 cable has been experimentally characterized in the frequency range between 90 kHz and 1 MHz, both in nominal conditions and in overheating situations generated by means of a climatic chamber. The changes in the electrical parameters of the cable modify the transmitted signal and the monitoring system proposed here allows the identification and localization of the overheated section with high accuracy.