학술논문

Non-Intrusive Voltage-Inversion Measurement Method for Overhead Transmission Lines Based on Near-End Electric-Field Integration
Document Type
article
Source
Energies, Vol 16, Iss 8, p 3415 (2023)
Subject
overhead line
electric-field integration method
non-intrusive voltage measurement
voltage-inversion measurement
Technology
Language
English
ISSN
16083415
1996-1073
Abstract
Existing electric-field integral inversion methods have limited field application conditions, and they are difficult to arrange electric-field measurement points on high-span overhead lines. This paper proposes a non-intrusive voltage measurement method for overhead transmission lines based on the near-end electric-field integration method. First, the electric-field distribution under 10 kV lines is calculated by finite element simulation software. The electric-field distribution of the plumb line and the discrete integral node below the wire are analyzed. Then, based on traditional electric-field integration, a line-voltage-inversion measurement method based on near-end electric-field integration is proposed. In addition, a voltage-monitoring system based on near-end electric-field integration is constructed. Next, the numerical integration types, the number of integration nodes, and the scale coefficient of the near-end region of the inversion algorithm are optimized with the electric-field simulation data. Finally, to verify the voltage-inversion method proposed in this paper, a test platform for overhead-line voltage is constructed using a MEMS electric-field sensor. The results indicate that the voltage-inversion error is 5.75%. The research results will provide theoretical guidance for non-intrusive voltage-inversion measurement of overhead lines.