Risk factors for contamination of hotel water distribution systems by Legionella species.
Document Type
Academic Journal
Author
Mouchtouri V; Department of Hygiene and Epidemiology, Faculty of Medicine, University of Thessaly, 22 Papakiriazi Str., Larissa 41222, Greece.; Velonakis ETsakalof AKapoula CGoutziana GVatopoulos AKremastinou JHadjichristodoulou C
Source
Publisher: American Society for Microbiology Country of Publication: United States NLM ID: 7605801 Publication Model: Print-Electronic Cited Medium: Print ISSN: 0099-2240 (Print) Linking ISSN: 00992240 NLM ISO Abbreviation: Appl Environ Microbiol Subsets: MEDLINE
Subject
Language
English
ISSN
0099-2240
Abstract
The Legionella colonization frequency at 385 Greek hotel hot and cold water distribution systems was 20.8%. Legionella contamination was associated with the presence of an oil heater (odds ratio [OR]=2.04, 95% confidence interval [CI]=1.12 to 3.70), with the sample temperature (OR=0.26, 95% CI=0.1 to 0.5), with seasonal operation (OR=3.23, 95% CI=1.52 to 6.87), and with the presence of an independent disinfection system (OR=0.30, 95% CI=0.15 to 0.62). The same water temperatures, free-chlorine levels, and pHs differently affect the survival of various Legionella spp.