학술논문

An Integral Fault Location Algorithm Based on a Modified T-Source Circuit Breaker for Flexible DC Distribution Networks.
Document Type
Article
Source
IEEE Transactions on Power Delivery. Oct2021, Vol. 36 Issue 5, p2861-2871. 11p.
Subject
*FAULT location (Engineering)
*FLEXIBLE printed circuits
*RADIAL distribution function
*ALGORITHMS
*ELECTRIC lines
*INTEGRALS
*FAULT currents
Language
ISSN
0885-8977
Abstract
Flexible DC distribution networks have been widely developed because of their advantages of high efficiency, low cost, and easy access to renewable energy. However, as distribution networks have more ends than the two-terminal transmission line, it is more challenging to protect them and locate their faults. Therefore, this paper proposes a modified T-source circuit breaker to protect against DC faults. Based on the proposed circuit breaker, an integral fault location method using double-terminal asynchronous data is proposed. The accuracy of the algorithm is not affected by the fault resistance. There are no differential terms in the algorithm, which greatly reduces the sensitivity to noise. The integral algorithm can remain steady when the voltage and current are zero in oscillation and attenuation periods. This constitutes the main contribution of this paper. Finally, it is verified by simulation and experiment that the proposed circuit breaker can isolate the power source within a short time in the typical DC distribution network. Under a noise of 30 dB for simulation, the location error of the proposed algorithm is <0.4% when the fault resistance is 0.5 Ω–500 Ω. [ABSTRACT FROM AUTHOR]