Ground current control scheme for back‐to‐back three‐phase T‐type rectifier and inverter systems.
Document Type
Article
Source
IEEJ Transactions on Electrical & Electronic Engineering. Nov2018, Vol. 13 Issue 11, p1649-1653. 5p.
Subject
*ELECTRIC inverters
*ELECTRIC power
*ROUTING (Computer network management)
*LIGHT transmission
*BLOCK diagrams
Language
ISSN
1931-4973
Abstract
This paper presents a method to control the ground current in a back‐to‐back connection of three‐phase T‐type rectifier and inverter stages if operated from a three‐phase mains with a grounded neutral point and a star‐connected three‐phase load with grounded star point. The proposed control scheme requires a ground current sensor and a single control loop, achieves a closed‐loop control system bandwidth of 1.7 kHz, and does not interact with the existing input phase current control system that is used to achieve sinusoidal mains currents. According to the presented experimental results, an effective reduction of the rms ground current from more than 200 mA (without controller) to less than 3 mA (with the proposed control scheme) is realized. © 2018 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc. [ABSTRACT FROM AUTHOR]