학술논문

Grid-Current Control With Inverter-Current Feedback Active Damping for LCL Grid-Connected Inverter
Document Type
Periodical
Source
IEEE Transactions on Industry Applications IEEE Trans. on Ind. Applicat. Industry Applications, IEEE Transactions on. 60(1):1738-1749 Jan, 2024
Subject
Power, Energy and Industry Applications
Signal Processing and Analysis
Fields, Waves and Electromagnetics
Components, Circuits, Devices and Systems
Power harmonic filters
Damping
Band-pass filters
Digital filters
Resonant frequency
Pulse width modulation
Inverters
Active damping
dual-loop grid-current control
grid-connected inverter
LCL filter
Language
ISSN
0093-9994
1939-9367
Abstract
The inverter-current proportional feedback (ICPF) active damping (AD) for an LCL grid-connected inverter (LCL-GCI) suffers from adverse gain reduction and loss of inductive ability in the low-frequency zone, making it unsuitable for active damping. To overcome the limitations of ICPF-AD, inverter-current bandpass filter feedback (ICBFF) AD is more conducive to suppressing the resonance of LCL-GCI. However, it is found that the system time delay constrains the damping capability of ICBFF-AD to resonance frequencies lower than those achievable with ICPF-AD. Therefore, this article proposes a second-order lead filter (SOLF) in cascade with the bandpass filter (BF) as an AD controller for inverter-current feedback AD. The analysis illustrates that cascading a SOLF with BF in the AD loop preserves the LCL filter's low-frequency gain and inductive nature resulting in improved dynamic response as compared to the ICPF-AD. Additionally, the cascaded filter AD allows the damping of higher resonance frequency with better noise immunity. The design approach for BF and SOLF is proposed and the effectiveness of the cascaded AD controller in the presence of different grid impedance is presented. The experimental results from a 10 kW laboratory setup corroborate the theoretical analysis.