학술논문

사무소건물의 LED조명기구 방열장치의 성능 분석 연구- 덕트 내 유량변화 중심으로 -
Performance of heat sinks for LED luminaires in office buildings - Focused on the variation of air flow rate in duct -
Document Type
Article
Source
KIEAE Journal, 14(6), 70, pp.81-86 Dec, 2014
Subject
건축공학
Language
한국어
ISSN
2288-9698
2288-968X
Abstract
In recent years, many researchers have considered the building energy consumption reduction accordingly to deal with abnormal climate changes and greenhouse gas reduction. However, the lighting energy use ratio has increased in spite of the development of the high efficiency lighting device. Therefore, the study aims to produce the LED lighting applications for the effective lighting heat removal by using the heat characteristics of LED lighting and analyzing the heat removal effect. In order to increase radiant heat efficiency, the heat pipe and heat sink was attached on PCB as LED lighting applications. Experiment was conducted to verify the temperature and air velocity of inside duct: thermocouples, anemometer. The heat removal effect of LED lighting applications was measured by observing the temperature of the lighting applications and the change of air velocity in duct. The experiment shows that the temperature change in the duct according to air velocity was 0.9~5.8℃. It is also concluded that heat removal was calculated from 33 to 81W.