학술논문

Partial discharge measurements in PWM inverter-driven low-voltage motors
Document Type
Conference
Source
2009 Australasian Universities Power Engineering Conference Power Engineering Conference, 2009. AUPEC 2009. Australasian Universities. :1-6 Sep, 2009
Subject
Power, Energy and Industry Applications
Partial discharge measurement
Pulse width modulation inverters
Voltage
Insulation
Coils
Partial discharges
Capacitance
Wounds
Stress
Cables
pulse-width modulated inverters
switching surges
electrical insulation
low votage motors
partial discharge
Language
Abstract
Partial discharge (PD) on low-voltage motors was not recognised as a potential issue until recently. Evolving converter technology has challenged the limit of LV insulation systems. Possible reliability issues have been recognised due to PDs, especially for inter-turn insulation. PD is related to the extension of standard 415V insulation systems to PWM inverter fed applications on 415V and 690V systems. The problem is exacerbated in inverter systems without dv/dt filters and run through long cables. This paper investigates the possibility of measuring PDs for such applications and aims to develop a practical insulation assessment methodology based on the IEC-TS 60034-18-41 proposal.