학술논문

A New Method for Dimensioning and Designing the Zero-Sequence Electromagnetic Filter Considering System Displacement Power Factor
Document Type
Periodical
Source
IEEE Transactions on Power Delivery IEEE Trans. Power Delivery Power Delivery, IEEE Transactions on. 35(3):1071-1082 Jun, 2020
Subject
Power, Energy and Industry Applications
Legged locomotion
Coils
Inductance
Power harmonic filters
Resistance
Electromagnetics
Magnetic flux
Mitigation
zero-sequence
dimensioning
designing
electromagnetic filter
Language
ISSN
0885-8977
1937-4208
Abstract
This paper proposes an innovative method for dimensioning and designing the zero-sequence electromagnetic filter applied to three-phase four-wire distribution power systems. As premises, the optimum ratio between zero-sequence and positive-sequence impedances of the filter must be established in order to potentiate the filtering percentage of zero-sequence currents and ensure the quality of the supply system displacement power factor. The calculations are based on the sequential harmonic transmittances of the equivalent circuit reduced to the coupling point of the electromagnetic filter. To validate the proposed method, the results obtained with the application of the electromagnetic filter designed in a test system using the MATLAB software are compared to the results of the system modeled in the PSIM software.