학술논문

Method for Assessing the Risk of Subsynchronous Oscillations in DFIG-Based Wind Parks
Document Type
Periodical
Source
IEEE Transactions on Power Delivery IEEE Trans. Power Delivery Power Delivery, IEEE Transactions on. 37(6):5071-5080 Dec, 2022
Subject
Power, Energy and Industry Applications
Capacitors
Generators
Integrated circuit modeling
Power system stability
Circuit stability
Power transmission lines
Oscillators
Control-to-grid interactions
subsynchronous oscillations
stability
wind generation
Language
ISSN
0885-8977
1937-4208
Abstract
The risk of unstable subsynchronous oscillations (SSO) in DFIG-based wind parks radially connected to transmission lines with series capacitive compensation is typically assessed with numerous electromagnetic transient (EMT) simulations, which is a time-consuming process. However, not all operating scenarios present risk of SSO and require such a detailed investigation. This paper proposes two charts based on impedance equivalents of wind generators obtained through frequency scans to quickly map which combinations of parameters can create unstable SSOs and which combinations are risk-free. With the information, engineers can immediately filter out scenarios with no risk of instability and conduct detailed studies on fewer scenarios that are truly critical. These charts can be obtained with simple equations that use only information readily available in practice to engineers, without the need to run any computer simulation. The charts also reveal the key operating conditions that can increase the risk of an unstable SSO and provide real-time quantitative insights into how close a wind park is to an instability. Application examples are provided to illustrate how this approach can help engineers speed up studies to identify the risk of SSO.